mcr MONSUN T-CWX
Model
mcr MONSUN T-CWX 90 T4 (A3:4) F400
Code

mcr MONSUN T-CWX 90 T4 (A3:4) F400

Axial fan 400ºC/2h

MANUFACTURING FEATURES

• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 400ºC/2h and ATEX Zone 2: fan: Ex h IIB T3 Gc and motor:Ex ec IIC T3 Gc. Standard voltages 400V(Y) 50Hz in three phase motors up to 3kW and 400V 50Hz for higher powers and 2 speed motors. IE3 efficiency motor from 0,75kW up to 45kW in single speed

APPLICATIONS

Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area and high pressures needed.
• Maximum working temperature: 60ºC.

UNDER REQUEST

• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0914

Fan

Max flow
48110 m³/h
mcr MONSUN T-CWX 90 T4 (A3:4) F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

mcr MONSUN T-CWX 90 T4 (A3:4) F400

Dimensions scheme
C (Mot.T.100L) C (Mot.T.112) C (Mot.T.132) C (Mot.T.160L) C (Mot.T.160L) C (Mot.T.160M) C (Mot.T.180L) C (Mot.T.180L) C (Mot.T.180M) C (Mot.T.180M) E O ØA ØB ØD ØJ
658 658 658 742 742 721 787 787 778 778 340 16x22,5º 1000 970 903.5 12

mcr MONSUN T-CWX 90 T4 (A3:4) F400

Electrical scheme

mcr MONSUN T-CWX 90 T4 (A3:4) F400

Model
PK 900
Code
Information
CONECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
KD 90
Code
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Fire classification: M0.

Model
WS
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
AB
Code
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
KSZ 90
Code
Information
SQUARE MOUNTING FRAME FOR FANS

MANUFACTURING FEATURES

• Square support frame for fans.
• Made of steel and protected against corrosion with polyester resin powder.

Model
SO2 900
Code
Information
Outlet protection guard for axial fans

MANUFACTURING FRATURES

• Protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.

UNDER REQUEST

• Stainless guard 304 or 316 with electro-polished finishing coat.

Model
SO1
Code
Information
INLET PROTECTION GUARD FOR AXIAL FANS

MANUFACTURING FRATURES

• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.

UNDER REQUEST

• Stainless guard 304 or 316 with electro-polished finishing coat.

Model
WS ATEX
Code
Information
ATEX SWITCH

Switch for ATEX environments. Suitable for zones 1-2 (gas) and 21-22 (dust), index protection IP65. Manufactured in aluminum alloy and RAL 7000 gray finishing coat. External screws in stainless steel. Control on the front. Tensions up to 690V. According to directive 2014/34 / UE (ATEX).