mcr MONSUN T-CHF-A
Model
mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400
Code

mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400

mcr MONSUN T-CHF-A

Centrifugal Roof Smoke Extraction Fan

 

Fire resistance class: F400 – 400°C / 120 min

Fan classified according to EN 13501-4

Performance properties in accordance with EN 12101-3

 

The mcr MONSUN T-CHF-A centrifugal roof smoke extraction fan is designed for single or two-speed operation for conveying and extracting hot smoke and heat in buildings. The fan is designed for installation on the building roof. The fan hood is made of UV-resistant material.

 

Technical data:

  •          Dimensions: D225 – D800 [mm]
  •          Protection rating: IP 55
  •          Nominal power: 0.12 kW – 7.5 kW
  •          Rotational speed: 750; 1500 rpm
  •          Operating mode: unidirectional
  •          Execution type: single-speed, two-speed

 

Additional information:

  •          Operation outside the smoke reservoir
  •          Mounting plate made of galvanized steel sheet
  •          Fan hood made of aluminum

 

 

Fan

Max flow
27090 m³/h
Weight
210 Kg

Motor

Power
4/1 kW
RPM Motor
960/470
I max. 400 V
11,77/3,39
Size
132M
Weight
53 Kg
Efficiency
70/64 %
FP
0,72/0,66
mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400

Dimensions scheme
A B aprox C D E F G H I K aprox
1134,6 1142,72 1035 840 9 453 468 50 31 593,72

mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400

Electrical scheme

mcr MONSUN T-CHF-A 800 T6/T12 4/1kW F400

Model
WS
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
AB
Code
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.