Centrifugal Roof Smoke Extraction Fan

 

Fire resistance class: F400 – 400°C / 120 min

Fan classified according to EN 13501-4

Performance properties in accordance with EN 12101-3

 

The mcr MONSUN T-CHF-A centrifugal roof smoke extraction fan is designed for single or two-speed operation for conveying and extracting hot smoke and heat in buildings. The fan is designed for installation on the building roof. The fan hood is made of UV-resistant material.

 

Technical data:

  •          Dimensions: D225 – D800 [mm]
  •          Protection rating: IP 55
  •          Nominal power: 0.12 kW – 7.5 kW
  •          Rotational speed: 750; 1500 rpm
  •          Operating mode: unidirectional
  •          Execution type: single-speed, two-speed

 

Additional information:

  •          Operation outside the smoke reservoir
  •          Mounting plate made of galvanized steel sheet
  •          Fan hood made of aluminum

 

 

Fan

Max flow
3590 m³/h
Weight
19 Kg

Motor

Power
0,55/0,09 kW
RPM Motor
1410/710
I max. 400 V
1,77/0,61
Size
80M
Weight
9.3 Kg
Efficiency
70/53 %
FP
0,70/0,49
mcr MONSUN T-CHF-A 355 T4/T8 0,55/0,09kW F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

mcr MONSUN T-CHF-A 355 T4/T8 0,55/0,09kW F400

Dimensions scheme
A B aprox C D E F G H I K aprox
664,6 644,6 665 520 9 253 210,8 40 30,75 363,25

mcr MONSUN T-CHF-A 355 T4/T8 0,55/0,09kW F400

Electrical scheme

mcr MONSUN T-CHF-A 355 T4/T8 0,55/0,09kW F400

Model
WS
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
AB
Code
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category