mcr MONSUN T-CCT
Model
mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400
Code

mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400

mcr MONSUN T-CCT

Axial Smoke Extraction Fan

 

Fire resistance class: F400 – 400°C / 120 min

Fan classified according to EN 13501-4

Performance properties in accordance with EN 12101-3

CSWU: 0370-CPR-7523

 

The mcr MONSUN T-CCT axial smoke extraction fan is designed for single or two-speed operation for conveying and extracting hot smoke and heat in buildings. The fan features a sound-absorbing galvanized steel casing with special removable insulation panels for easy access to the motor and convenient maintenance. The housing has an epoxy powder-coated finish. 

Technical data:

  •          Dimensions: D400 - D1250 [mm]
  •          Protection rating: IP 55
  •          Nominal power: 0.55 kW – 37 kW
  •          Rotational speed: 750; 1000; 1500; 3000 rpm
  •          Operating mode: unidirectional, reversible
  •          Execution type: single-speed, two-speed 

 

Additional information:

  •          Operation inside and outside the smoke reservoir
  •          Box-type housing, thermally and acoustically insulated
  •          Fan available in EX (ATEX) version

Fan

Max flow
54810 m³/h
mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400

Dimensions scheme
A B C D E F G H J K L O
1181 1176 863.3 649.6 106.85 995 90.65 27 1480.5 1380 80 20

mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400

Electrical scheme

mcr MONSUN T-CCT 90 T4/T8 (A3:8) F400

Model
WS
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
AB
Code
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
AM
Code
Information
ANTI-VIBRATION SPRING BLOCK

MANUFACTURING FEATURES

• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:

Arrow (mm.)          r.p.m.
    20 mm          >600 r.p.m.
    30 mm          >500 r.p.m.

• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.

APPLICATION

• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.

Model
WO 90-100
Code
Information
OUTDOOR FLANGE WITH BIRD GUARD FOR mcr MONSUN F-CCT

MANUFACTURING FEATURES

• Outdoor flange with bird guard for mcr MONSUN F-CCT.
• Made of galvanized Steel.